The QSE-CI-DMX operates either in a standalone QS system, a Quantum system, an Athena system, or a HomeWorks system. It performs different functions depending on the system in which it is operating. QS Standalone System The QSE-CI-DMX control interface allows zones on a GRAFIK Eye QS to control DMX512-controlled devices. Any zone on the GRAFIK Eye QS can be mapped to either a single DMX512 channel or to three separate DMX512 channels, for RGB / CMY colour-control applications. Quantum, Athena, or HomeWorks Systems The DMX channels (maximum of 32) are mapped to Quantum, Athena, or HomeWorks zones, and can be programmed as 1-channel lighting, 1-channel integration, or 3-channel RGB / CMY. If the QSE-CI-DMX is part of a Quantum or HomeWorks system, GRAFIK Eye QS zones cannot be programmed to control DMX channels.

Features

• Map any zone on a GRAFIK Eye QS control unit (in QS Standalone systems) or any zone in a Quantum, Athena, or HomeWorks system to any single DMX512 channel

• Map any zone on a GRAFIK Eye QS control unit, any Quantum zone, Athena zone, or any HomeWorks zone simultaneously to three DMX512 channels for RGB / CMY colour-control

• Integral RGB / CMY lookup table that maps GRAFIK Eye QS zone intensities, Quantum zone intensities, Athena zone intensities, or HomeWorks zone intensities to RGB / CMY values (colours)

• RGB / CMY table can be customized by using the Lutron QS Colour Configuration Tool (PC application available at www.lutron.com/qs) within the HomeWorks Designer, Quantum Q-Design, or Athena design software.

Power Requirements

• Low-voltage SELV / PELV / NEC® Class 2

• Operating Voltage: 24–36 V- 65 mA

Environment

• 32 °F to 104 °F (0 °C to 40 °C).

• Relative humidity less than 90% non-condensing.

• Unit generates heat, maximum 8 BTU / hr.