LQSE-4A5-230-D

Lutron

Details

PRO LED+ Phase Adaptive Power Module

Enquire
Category: Tag:

Additional information

Brand

The DIN Power Module (DPM) family is a group of modular products for the control of lighting loads and motor loads. This document describes the following product: LQSE-4A5-230-D: 4-Zone DIN Power Module for phase control dimming of lighting loads

Features

• Can be used in HomeWorks and HomeWorks QS systems.

• Includes QS link for seamless integration of lights and controls.

• An auto-detect mode is available to detect and configure forward-phase or reverse-phase (leading-edge or trailing-edge) dimming for incandescent / halogen, electronic / magnetic low voltage and neon / cold cathode light sources.

• A locked forward-phase or reverse-phase (leadingedge or trailing-edge) mode is available.

• Controls dimmable LED loads. Refer to www.lutron.com/ledtool for compatibility with dimmable LED light sources.

• RTISS technology compensates for incoming mains voltage variations such as changes in Root Mean Square (RMS) voltage, frequency shifts (up to ± 2% change in frequency /second), harmonics and line noise.

• RTISS-TE technology allows for true instantaneous voltage compensation for incoming mains voltage variations. Only operates in reverse-phase (trailing edge) when “voltage-comp.” is enabled.

• RTISS-ICM technology is able to withstand highinrush LEDs, bulb blowouts, and direct shorts.

• Provides air gap off (when all zones are off).

• Integral protection for common temporary over-current and over-voltage conditions.

• LEDs on the module provide diagnostic information.

Power

• 220 – 240 V~ 50/60 Hz

• 10 A maximum total input current.

• Lightning strike protection meets ANSI/IEEE standard 62.31-1980. Can withstand voltage surges of up to 6000 V and current surges of up to 3000 A.

• Contact Lutron for applications where the electrical distribution system does not have a connection to earth, an IT network per IEC 60364, such as an ungrounded Delta feed.

Regulatory Approvals

• Lutron Quality Systems registered to ISO 9001.2015

• RoHS Compliant

• CE marked

• UKCA marked

• Rated for 150 W of LEDi per IEC 60669

Environment

• Relative humidity: less than 90% non-condensing.

• For indoor use only.

Output Zone Ratings

• Each zone has no minimum load requirement.

• When programmed to “auto detect” mode, the module starts in reverse-phase (trailing-edge) and if an incompatible load is detected, it will convert to forward-phase (leading-edge).

• Internal relay provides an air gap off when all zones are off.

• One load type per zone.

• Output must not be used to control general purpose receptacles.